1SDA051224R1 ABB SACE TMAX T2H 160 Moulded Case Circuit Breaker for Industrial Use **NEW**

ABB SKU: P-AB-M-0493

$285.00

Tax included

Only 1 left!

Extended Product Type:
T2H 160 MA52 Im=312...624 3p F F
Product ID:
1SDA051226R1
EAN:
8015644516468
Catalog Description:
T2H 160 MA52 Im=312...624 3p F F
Long Description:
C.BREAKER TMAX T2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MA Iu 52 A Im312...624
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T2H complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Poles
3-poles (3P3d)
Rated current
20A (160 oversized frame)
Trip current rating
20 AT
Frame current rating
160 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
500Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
800 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
70kA (380Vac)
70kA (415Vac)
55kA (440Vac)
36kA (500Vac)
8kA (690Vac)
70kA (250Vdc; 2 poles in series)
85kA (250Vdc; 3-poles in series)
70kA (500Vdc; 3-poles in series)
Trip unit type
Technology = Magnetic only
Series = MA (adjustable)
Display = none
Protection functions
Magnetic protection (Short-circuit)
Protection settings
Short-circuit pickup current -- adjustable 120A...240A
Operating mode
Toggle
Electrical durability (with load)
8000 operations
Mechanical durability (at no load)
25000 operations
Power dissipation/losses
(1-pole) 1.7 W
Order code / Manufacturer SKU
T2H 160 MA20 Im=120...240 3p F F
Manufacturer product status
Commercialized
Equivalent to
T2H160MA20Im1202403pFF
EAN code
8015644516444
UNSPSC code
39121616
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)